Domain 1: Conductors and Cables

Question 1

Three two-wire, 240 V circuits share a 75 ft EMT run. Each circuit has two 8 AWG copper THHN conductors and one equipment grounding conductor; there are no neutrals. Ambient temperature is 40°C and all power terminals are rated 75°C. Table 310.16 gives 8 AWG copper ampacities of 50 A at 75°C and 55 A at 90°C. The 90°C ambient correction factor is 0.91; adjustment factors are 0.80 for 4-6 current-carrying conductors and 0.70 for 7-9. What is each 8 AWG conductor's allowable ampacity, to the nearest tenth of an ampere?

Show answer & explanation

Correct answer: B - 40.0 A

Domain 2: Electrical Power

Question 2

At a commercial service identified as 240/120 V, three-phase, four-wire delta, a qualified electrician records 240 V between every pair of phases. Measurements to neutral are A-N 120 V, B-N 208 V, and C-N 120 V. A new control requires a 120 V line-to-neutral supply. Which response correctly uses these findings?

Show answer & explanation

Correct answer: A - Use A-N or C-N for the control; B-N is the expected high-leg voltage.

Domain 3: Fire Detection and Alarm Systems

Question 3

During a tenant renovation, a convenience receptacle is added to the 120 V branch circuit supplying a power-limited fire-alarm control unit. The control unit's backup batteries remain functional. Its breaker already has the required identification and labeling. What must change to satisfy the NEC fire-alarm power-supply rule?

Show answer & explanation

Correct answer: D - The convenience receptacle must be moved to another branch circuit.

Domain 4: General Electrical Knowledge

Question 4

While checking an operating 120 V heater, a journeyman closes an AC clamp meter around both the hot and neutral conductors together. It reads approximately zero, although the heater continues producing heat. The same meter reads normally around a single conductor on another loaded circuit. How should the zero reading be interpreted?

Show answer & explanation

Correct answer: D - The opposing currents cancel in the clamp; measure one conductor to obtain load current.

Domain 5: Grounding and Bonding

Question 5

A new 120/240 V feeder supplies a detached workshop through PVC conduit with two ungrounded conductors, an insulated neutral, and a wire-type equipment grounding conductor. The workshop's grounding electrodes and feeder equipment grounding conductor connect to a grounding bar bonded to the panel enclosure. Inspection finds the panel's neutral bonding screw installed, and ordinary load current is flowing on the feeder equipment grounding conductor. After safe isolation, what correction addresses this defect?

Show answer & explanation

Correct answer: B - Remove the neutral bonding screw while retaining the enclosure's equipment-grounding connection.

Domain 9: Motors

Question 6

A three-wire motor starter runs the motor while START is held but drops out immediately when START is released. The normally closed STOP and overload contacts have been verified closed, and the contactor coil receives its rated voltage while START is held. A normally open auxiliary contact is wired across START. Which fault best fits these observations?

Show answer & explanation

Correct answer: A - An open auxiliary holding-contact circuit

Domain 11: Raceways and Boxes

Question 7

A box receives three 12/2 cables with grounds. All six insulated 12 AWG conductors are spliced or terminated inside. The box also contains the three 12 AWG equipment grounding conductors, internal cable clamps, and one duplex receptacle on a single yoke. Two 12 AWG insulated pigtails remain entirely inside the box. There are no other fittings or devices. Using 2.25 cubic inches per 12 AWG allowance, what minimum box volume does the 2023 NEC require?

Show answer & explanation

Correct answer: C - 22.50 cubic inches

Domain 12: Safety Information

Question 8

Before replacing a 480 V starter, a qualified electrician isolates and locks out all identified sources. An appropriately rated contact voltage tester responds correctly on a known live source, then reads zero on every required conductor-to-conductor and conductor-to-ground check at the starter. When rechecked on an independently confirmed live source, the tester now reads zero. What does this mean for permission to touch the conductors?

Show answer & explanation

Correct answer: A - Absence of voltage is unproven; repeat the complete verification with a functioning tester.

Domain 13: Service, Feeders, and Branch Circuits

Question 9

A new dwelling kitchen has a dedicated 120 V, 20 A branch circuit supplying only a refrigerator receptacle, 9 ft from the sink. The receptacle does not serve a countertop. For this circuit, the 2023 NEC requires which protection in addition to ordinary overcurrent protection?

Show answer & explanation

Correct answer: D - Both GFCI and AFCI protection

Domain 14: Special Occupancies and Equipment

Question 10

A 240 V condensing unit is marked minimum circuit ampacity (MCA) 28 A and maximum circuit breaker 40 A. Its 10 AWG copper THWN-2 conductors have 35 A usable ampacity after termination limits and all applicable corrections. The listed 40 A breaker starts the unit reliably. Which assessment of this installation is correct?

Show answer & explanation

Correct answer: C - The conductors and breaker satisfy their separate nameplate requirements; neither must be changed.