Question 1
Three two-wire, 240 V circuits share a 75 ft EMT run. Each circuit has two 8 AWG copper THHN conductors and one equipment grounding conductor; there are no neutrals. Ambient temperature is 40°C and all power terminals are rated 75°C. Table 310.16 gives 8 AWG copper ampacities of 50 A at 75°C and 55 A at 90°C. The 90°C ambient correction factor is 0.91; adjustment factors are 0.80 for 4-6 current-carrying conductors and 0.70 for 7-9. What is each 8 AWG conductor's allowable ampacity, to the nearest tenth of an ampere?
Show answer & explanation
Correct answer: B - 40.0 A